Delta Electronics AH — MC_ReadStatus

AH Motion Controller – Motion Control Instructions Manual _3  Outputs Update Timing 3-128 Name Function Data type Output range (Default value) Disabled Programming of AH Motion Controller – Operation Manual for the state diagram.

BOOL True/False (False) Stopping BOOL True/False (False) Homing BOOL True/False (False) Standstill BOOL True/False (False) DiscreteMotion BOOL True/False (False) ContinousMotion BOOL True/False (False) SyncMotion BOOL True/False (False) Coordinated BOOL True/False (False) CoordinatedStop BOOL True/False (False) CoordinatedHalt BOOL True/False (False) Name Timing for shifting to True Timing for shifting to False Valid  When Enable shifts to True and the axis state at the output is available.  When Enable shifts to False.  When Error shifts to True. Busy  When Enable shifts to True.  When Enable shifts to False.  When Error shifts to True.

Error/ErrorID  When an error occurs in the execution conditions or input values for the instruction.(Error code is recorded)  When Enable shifts from True to False. (Error code is cleared) ErrorStop  When the axis status indicates “ErrorStop”.  When the axis status did not indicate “ErrorStop”. Disabled  When the axis status indicates “Disabled”.  When the axis status did not indicate “Disabled”. Stopping  When the axis status indicates “Stopping”.  When the axis status did not indicate “Stopping”. Homing  When the axis status indicates” Homing”.  When the axis status did not indicate “Homing”. Standstill  When the axis status indicates “Standstill”.

 When the axis status did not indicate “Standstill”. DiscreteMotion  When the axis status indicates “DiscreteMotion”.  When the axis status did not indicate “DiscreteMotion”. ContinousMotion  When the axis status indicates “ContinousMotion”.  When the axis status did not indicate “ContinousMotion”. SyncMotion  When the axis status indicates  When the axis status did not indicate