Delta Electronics AH — DFB_CamCurve2

AH Motion Controller – Motion Control Instructions Manual  Outputs Update Timing _3  Timing Diagram Execute Done Busy Error Error ID *Note: Kn refers to the maximum supported axes of different models. For example, AH20EMC-5A supports K1~K32. 3-228 SyncBegin The starting point to synchronizate LREAL K0~K2147483647(0) SyncEnd The stopping point to synchronizate LREAL K0~K2147483647(0) Name Timing for shifting to True Timing for shifting to False Done  When the specified cam point is written into the cam curve.  When Execute shifts from True to False.  When Error shifts to True. Busy  When Execute changes to True.  When Done shifts to True.  When Error shifts to True.

Error/ErrorID  When an error occurs in the execution conditions or input values for the instruction. (error code is recorded)  When Execute shifts from True to False. (error code is cleared) SyncBegin  When Done shifts to True.  When Done shifts to True. SyncEnd  When Done shifts to True.  When Done shifts to True.