AH Motion Controller – Motion Control Instructions Manual DFB_ECATServoRead  Inputs _3  Outputs 3-308 FB/FC Description FB DFB ECATServoRead reads the values of parameters from the Delta servo drive specified on an _ EtherCAT network. Name Function Data type Setting value Timing for updating (Default value) Execute Executes the instruction when Execute changes to True. The value of the specified parameter will then be read from the servo drive. BOOL True/False (False) - Group Group number (Please refer to the user manual of the applied Delta servo drive for more information.) WORD 0~9 (0) When Execute shifts to True and Busy is False.

Parameter Parameter number (Please refer to the user manual of the applied Delta servo drive for more information.) WORD 0~99 (0) When Execute shifts to True and Busy is False. Retry Number of times for auto-retry when an error occured on reading the parameter values. WORD 0~65535 (0) When Execute shifts to True and Busy is False. Name Function Data type Output range (Default value) Done True when the specified data is read. BOOL True/False (False) Busy True when the instruction is executed. BOOL True/False (False) Error True if an error occurs. BOOL True/False (False) ErrorID Indicates the error code if an error occurs. Refer to Appendices for error code descriptions.

DWORD 16#0~16#FFFFFFFF (0)