Appendix 6. Data Type Unit: Enum A2_ A-33 Error code Description CPU Status LED indicator status ERROR BUS FAULT 16#6004 The IP address filter is set incorrectly. (SM1108) Continue Blinking Keep 16#6006 The static ARP table is set incorrectly. (SM1108) Continue Blinking Keep 16#600D The RJ45 port is not connected. (SM1100) Continue Keep Keep 16#620D The length of the data which needs to be sent in a UDP Socket Configuration window is illegal. Continue Keep Keep 16#6212 There is no response from the remote device after the timeout period. Continue Keep Keep 16#6213 The data received exceeds the limit. Continue Keep Keep 16#6214 The remote device refuses the connection.
Continue Keep Keep 16#6400 The number of TCP connections reaches the upper limit, or the flag which is related to the sending of the data is not set to ON. Continue Keep Keep 16#6401 The remote device aborts the connection. Continue Keep Keep 16#6402 There is no response from the remote device after the timeout period. Continue Keep Keep 16#6403 The remote IP address used in the applied instruction is illegal. Continue Keep Keep 16#6404 The MODBUS function code not supported is received. Continue Keep Keep 16#6405 The number of data which will be received is not consistent with the actual length of the data.
Continue Keep Keep 16#6501 The remote device involved in the data exchange does not respond after the timeout period. (SM828~SM955) Continue OFF OFF 16#6502 The remote device involved in the data exchange does not respond correctly. (SM828~SM955) Continue OFF OFF 16#6700 MODBUS TCP data exchange initialization error Continue Keep Keep 16#6701 MODBUS TCP data exchange timeout Continue Keep Keep 16#6702 MODBUS TCP data receiving error Continue Keep Keep 16#7002 This function is not available for CPU modules. Continue Keep Keep