Delta Electronics AH — AH20MC-5A

AH Motion Controller – Motion control Instructions Manual AH20MC-5A _A2 A-44 Error code Description LED indicator status CPU Module BUS FAULT Error 16#A01B General program error Blinking 16#A01C LD/LDI has been used more than nine times. Blinking 16#A01D There is more than one level of nested program structure supported by RPT/RPE. Blinking 16#A01E SRET is used between RPT and RPE. Blinking 16#A01F There is no M102 in the main program, or there is no M2 in the motion program. Blinking 16#A020 The wrong instruction is used, or the device used exceeds the range. Blinking Error code Description LED indicator status CPU Module BUS FAULT ERROR 16#A002 The subroutine has no data.

Blinking 16#A003 CJ, CJN, and JMP have no matching pointers. Blinking 16#A004 There is a subroutine pointer in the main program. Blinking 16#A005 Lack of the subroutine Blinking 16#A006 The pointer is used repeatedly in the same program. Blinking 16#A007 The subroutine pointer is used repeatedly. Blinking 16#A008 The pointer used in JMP is used repeatedly in different subroutines. Blinking 16#A009 The pointer used in JMP is the same as the pointer used in CALL. Blinking 16#A00B Target position (I) of the single speed is incorrect. Blinking 16#A00C Target position (II) of the single-axis motion is incorrect. Blinking 16#A00D The setting of speed (I) of the single-axis motion is incorrect.

Blinking 16#A00E The setting of speed (II) of the single-axis motion is incorrect. Blinking 16#A00F The setting of the speed (V ) of returning to zero is incorrect. RT Blinking 16#A010 The setting of the deceleration (V ) of returning to zero is incorrect. CR Blinking 16#A011 The setting of the JOG speed is incorrect. Blinking