Appendix 6. Data Type Unit: Enum A2_ A.2.3. Troubleshooting for Limitation Errors Troubleshooting for the software limit errors The controller system checks the software limits before or during the motion by the error code 0x3911. When the operation exceeds the software limits, the error code will be indicated and the axis will enter “ErrorStop”. Servo drive will not report this error since the error handling in this case is controlled by the controller. Note: for details on the softwaere limit setups, refert to ISPSoft manual. Do not set the values too close to the value of the software upper limit.
A-97 Error code Description Remedy 16#A0F1 No slave station is added to the node list in CANopen builder. Add slave stations to the node list, and download the configuration to AH10COPM-5A. 16#A0F3 An error occurs in AH10COPM-5A. Download parameters again. If the error still occurs, please replace AH10COPM-5A. 16#A0F4 The bus used is off. Please check whether the bus cable on the CANopen network created is connected correctly, make sure that the serial transmission speeds of all the nodes on the network are the same, and power AH10COPM-5A again. 16#A0F5 The node address of AH10COPM-5A is set incorrectly. The node address of AH10COPM-5A must be in the range of 1 to 127.
16#A0F6 Internal error: An error occurs in the manufacturing process in the factory. Power AH10COPM-5A again. If the error still occurs, please replace AH10COPM-5A. 16#A0F7 Internal error: GPIO error 16#A0F8 Hardware error 16#A0F9 Low voltage Make sure that the power supplied to AH10COPM-5A is normal. 16#A0FA An error occurs in the firmware of AH10COPM-5A. Power AH10COPM-5A again. 16#A0FB The transmission registers in AH10COPM-5A are full. Please make sure that the bus cable on the CANopen network created is connected correctly, and power AH10COPM-5A again. 16#A0FC The reception registers in AH10COPM-5A are full.
Please make sure that the bus cable on the CANopen network created is connected correctly, and power AH10COPM-5A again.