Mitsubishi — 5.2.1 Precautions

AH500 Hardware Manual parasitic capacitance, and the system will break down.  Grounding a cable Please ground a cable according to the steps below. (1) Please ground a cable correctly. (2) The area of the cross-section of the cable which is grounded should be 2 mm 2 or larger than 2 mm 2 . (3) The ground point should be near the PLC. Ground the cable properly. Note (1) The 110 V/220 V power cable and the 24 VDC power cable should be thick cables. (The area of the cross-section of the cable is 2 mm 2 , and the diameter of the cable is 14 AWG.) Be sure to twist the power cables at terminal screws.

To prevent the short circuit which results from loose screws, users need to use solderless terminals with insulation sleeves. (2) If cables are connected to the terminals LG and FG, the cables need to be grounded. Do not connect LG and FG to any devices. If LG and FG are not grounded, the PLC will be susceptible to noise. Since LG have potential, users will get an electric shock if they touch metal parts. 5.2 Connecting Power Cables 5.2.1 Precautions  Connecting AC power cables (1) Please separate the power cable of AHPS05-5A from the power cables for I/O devices and other devices. If there is much noise, connect an isolating transformer.

Isolating transformer AHPS05-5A AC power supply 100-240 V I/O equipment Another piece of equipment (2) The 110 VAC cable, the 220 VAC cable, and the 24 VDC cable should be twisted, and connected to a module within a short distance. (3) Do not bundle 110 VAC cable, the 220 VAC cable, the 24 VDC cable, the (high-voltage high-current) main circuit, and the I/O signal cable together. Besides, it is recommended that the distance between adjacent cables should be more than 100 millimeters. (4) To prevent the surge resulting from lightning, please install a surge absorber in the way shown below. Surge absorber AHPS05-5A I/O equipment AC power supply 100-240V Points for attention: 1.

The surge absorber and the PLC system should be grounded separately. 2. Please select the surge absorber whose working voltage is not less than the maximum allowable input voltage. 5-4