Mitsubishi — 5.5.2.2 Relay Output Circuit

AH500 Hardware Manual 3. TRIAC output Load through which the alternating current flows 5.5.2.2 Relay Output Circuit Relay terminals have no polarity. They can be applied to alternating current which passes through a load, or direct current which passes through a load. The maximum current which can passes through every relay terminal is 2 A, and the maximum current which can passes through every common terminal is 5 A. The lifetime of a relay terminal varies with the working voltage, the load type (the power factor cos ψ ), and the current passing through the terminal. The relation is shown in the life cycle curve below.

2000 3000 1000 0.4) ψ = =0.4) ψ Operation(X10 ) 3 500 200 300 100 50 30 20 0.5 0.1 0.2 0.3 0.7 1 2 Contact Current(A)  Relay output circuit 5-40 120V AC Res istive 30VD C Indu ctive(t=7 24 24 0VAC I nductive( 120V 120V AC Induc 30VDC Inductive (t=40m s) ① Direct-current power supply ② Emergency stop: An external switch is used. ③ Fuse: To protect the output circuit, a fuse having a breaking capacity in the range of 5 A to 10 A is connected to the common terminal. ④ Alternating-current power supply