Mitsubishi — 5.10.4.1 Wiring Input Terminals

AH500 Hardware Manual 5.10.4.1 Wiring Input Terminals The input signal is the direct-current power input. Sinking and sourcing are the current driving capability of a circuit. They are defined below.  Sinking Direct current The current flows into the common terminal S/S. I/O Equivalent circuit of the input circuit X0.8 Internal circuit S/S  Sourcing Direct current The current flows from the common terminal S/S.

Equivalent circuit of the input circuit X0.8 I/O Internal circuit S/S  Wiring the differential input terminals The direct-current signals ranging in voltage from 5 V to 24 V can pass through the high-speed input terminals X0.0+~X0.3+ and X0.0-~X0.3- on AH10PM-5A, and X0.0+~X0.3+, X0.0-~X0.3-, X0.8+~X0.9+, and X0.8-~X0.9- on AH15PM-5A. (Only 24 VDC signals can pass through the other input terminals on AH10PM-5A and AH15PM-5A.) The frequency of input signals can be up to 200 kHz. If the frequency of input signals is less than 50 kHz and there is not much noise, these high-speed input terminals can be connected to the direct-current power supply whose voltage is in the range of 5 V to 24 V.

The wiring diagrams for AH10PM-5A are shown below. Sinking: 5-82