AH500 Hardware Manual 5.10.5.1 Wiring the Differential Input Terminals The direct-current signals ranging in voltage from 5 V to 24 V can pass through the high-speed input terminals X0.0+~X0.3+, X0.0-~X0.3-, X0.8+~X0.15+, and X0.8-~X0.15- on AH20MC-5A. The frequency of input signals can be up to 200 kHz. These high-speed input terminals are connected to a differential (two-wire) line driver.
Wiring differential input terminals (The wiring below is used for high speed and high noise.) Encoder output AH20MC-5A high speed input - 5.10.5.2 Transistor Output Circuit 5-92 A+ A A- B+ B B- X0 X0 X0 X0 .0+ .0- .1 + .1 - AH20MC-5A Load Trigger Y0.8 Direct-current power supply Emergency stop Fuse The output terminals of a transistor module are open-collector output terminals. If Y0.8 is a pulse train output terminal of a transistor module, the output current passing through its output pull-up resistor must be greater than 0.1 A to ensure that the transistor module operates normally. A relay or a solenoid valve is used as a DC load.
A diode is connected in parallel to absorb the surge voltage which occurs when the load is OFF.