Mitsubishi — 7.1.1 EMC Standards Applicable to an AH500 System

AH500 Hardware Manual 7.1 EMC Standards for an AH500 System 7.1.1 EMC Standards Applicable to an AH500 System The EMC standards which are applicable to an AH500 system are listed below.

 EMI  EMS  Conducted immunity test 7-2 Port Frequency range Level (Normative) Reference standard Enclosure port ) 30-230 MHz 40 dB (μV/m) quasi-peak IEC 61000-6-4 (radiated) (measured at a 230-1000 MHz 47 dB (μV/m) quasi-peak distance of 10 meters AC power port (conducted) 0.15-0.5 MHz 79 dB (μV) quasi-peak IEC 61000-6-4 66 dB (μV) average 0.5-30 MHz 73 dB (μV) quasi-peak 60 dB (μV) average Environmental Reference Test Test level phenomenon standard Electrostatic IEC 61000-4-2 Contact ± 4 kV discharge Air ± 8 kV Radio frequency IEC 61000-4-3 80% AM, 1 kHz sinusoidal 2.0-2.7 GHz 1 V/m electromagnetic field 1.4-2.0 GHz 3 V/m Amplitude modulated 80-1000 MHz 10 V/m Power frequency IEC 61000-4-8 60 Hz 30 A/m magnetic field 50 Hz 30 A/m Environmental phenomenon Fast transient High energy surge Radio frequency burst interference Reference standard IEC 61000-4-4 IEC 61000-4-5 IEC 61000-4-6 Interface/Port Specific Test level Test level Test level interface/port Data communication Shielded cable 1 kV 1 kV CM 10V Unshielded cable 1 kV 1 kV CM 10V Digital and analog I/O AC I/O (unshielded) 2 kV 2 kV CM 1 kV DM 10V Analog or DC I/O(unshielded) 1 kV 1 kV CM 10V All shielded lines (to the earth) 1 kV 1 kV CM 10V Equipment power AC power 2 kV 2 kV CM 1 kV DM 10V DC power 2 kV 0.5 kV CM 0.5 kV DM 10V I/O power and auxiliary power output AC I/O and AC auxiliary power 2 kV 2 kV CM 1 kV DM 10V DC I/O and DC auxiliary power 2 kV 0.5 kV CM 0.5 kV DM 10V