Mitsubishi — 9.1.4 BUS FAULT LED Indicator’s Blinking

AH500 Hardware Manual 9.1.4 BUS FAULT LED Indicator’s Blinking If the BUS FAULT LED blinks, please check the operating state of the module. Please refer to sections 12.4.2~12.4.8 in AH500 Operation Manual for more information about the LED indicators, and section 9.2 in this manual for more information about the troubleshooting for I/O modules. 9-10 Error Description Remedy code 16#1401 An error occurs when the data in the I/O module is accessed. (SM9) Please contact the factory. 16#1402 The actual arrangement of the I/O modules is not consistent with the module table. (SM9) Check whether the module table in HWCONFIG is consistent with the actual arrangement of the I/O modules.

16#1403 An error occurs when the data is read from the module. (SM9) Check whether the module operates normally. If the error still occurs, please contact the factory. 16#1405 The setting parameter of the module is not found. (SM9) Set the parameter in HWCONFIG again, and download it. 16#1407 A communication error occurs when the data is accessed through the auxiliary processor. (SM9) Check whether there is noise, and eliminate the noise. If the error still occurs, please contact the factory. 16#1409 The extension backplane is disconnected. (SM9) 1. Check whether the extension backplane is connected properly. 2.

Check whether the extension backplane operates normally, and make sure that the extension backplane is not affected by noise. 16#140A The communication with the extension backplane is incorrect. (SM9) 1. Check whether the extension backplane is connected properly. 2. Check whether the extension backplane operates normally, and make sure that the extension backplane is not affected by noise. 16#140B The number of network modules exceeds the limit. (SM9) Please decrease the number of network modules to the number supported by the system. 16#140C The checksum of the high-speed data exchange is incorrect. Please check the version of the firmware installed on the module, and contact the factory.

16#140D The ID of the actual power supply module is not the same as the ID of the power supply module set in HWCONFIG. Check whether the ID of the power supply module set in HWCONFIG is the same as the ID of the actual power supply module. 16#140E The amount of data exchanged at a high speed exceeds the maximum amount supported. Please check the version of the firmware installed on the module, and contact the factory. 16#140F High-speed data exchange error Please check the version of the firmware installed on the module, and contact the factory.