Chapter 12 Network Module AH10PFBM DP LED DP LED displays if the communication between AH10PFBM-5A and PROFIBU DP slaves is normal. 12.7.2 Digital Display The digital display displays the state of AH10PFBM-5A. 12-53 LED status Indication How to correct Green light on Master makes the connection with the slave -- Green light flickers The configuration in the module is empty. Download the appropriate configuration first. Contact the factory if the error still exists. Red light on All slaves are offline. 1. Detect if the PROFIBUS DP bus connection is proper. 2. Detect if either end of the network is added the terminal resistor. Red light flickers At least one slave is offline 1.
Detect if the PROFIBUS DP bus connection is proper. 2. Detect if both ends of the network have connected the terminal resistors respectively. Code Indication How to correct 0~ 7D When AH10PFBM-5A works normally, the digital display displays its node address. -- 80 AH10PFBM-5A is in STOP status. Turn the RUN/STOP switch of PLC to RUN or check if the hardware configuration in AH PLC is consistent with that in the actual rack. E2 AH10PFBM-5A detects that one slave is offline. 1. Detect if the PROFIBUS DP bus connection is proper. 2. Detect if both ends of the network have connected the terminal resistors respectively.
E6 An error of some modules connected to AHRTU- PFBS-5A is detected by the master. Check the modules connected to AHRTU-PFBS- 5A. F1 The configuration in the master module is empty. Download the appropriate configuration. F2 PLC does not assign the I/O mapping area to the master Assign the appropriate I/O mapping area to the master via ISPSoft F3 Master enters test mode Re-power it. F4 Master initializing error Contact the factory if the error still exists after re- powering 10PFBM. F5 Timeout for the communication between chips inside master Contact the factory if the error still exists after re- downloading the appropriate configuration.
F6 Internal storage unit error Contact the factory if the error still exists after re- powering 10PFBM. F7 Data exchange unit error Contact the factory if the error still exists after re- powering 10PFBM. F8 the master serial number detection error Contact the factory if the error still exists after re- powering 10PFBM. FB Timeout for the data exchange with PLC Contact the factory if the error still exists after re- powering 10PFBM.