Kaiyi — 13.8.4 Diagnosis via ISPSoft

AH500 Module Manual The meanings of error codes in AH10PFBS-5A shown in the system log of PLC are listed in the following table. 13-14 Error code Indication How to deal with it 16#A0F0 The node address of AH10PFBS-5A exceeds the valid range. Set the node address of AH10PFBS-5A between 1~125. 16#A4F1 Internal hardware error If the error still exists after repowering AH10PFBS- 5A, replace it with a new one. 16#A4F2 Parameter error Check if the GSD file AH10PFBS-5A is using is correct. 16#A4F3 Configuration error Check if the GSD file AH10PFBS-5A is using is correct. 16#A4F4 GPIO detection error If the error still exists after repowering AH10PFBS- 5A, replace it with a new one.

16#A4F5 AH10PFBS-5A enters the mode of factory test. Repower AH10PFBS-5A after setting its node address between 1~125. 16#A4F6 1. AH10PFBS-5A has not been connected to the PROFIBUS-DP network. 2. PROFIBUS-DP master has not configured AH10PFBS-5A slave or the configured node address of AH10PFBS- 5A is inconsistent with that of the actually connected one. 1. Check if the communication cable between AH10PFBS-5A and PROFIBUS-DP master is in normal status. 2. Ensure that AH10PFBS-5A slave has been configured to PROFIBUS-DP master and the configured node address of AH10PFBS-5A is consistent with that of the actually connected one. 3. Check if PROFIBUS-DP master works normally.