Kaiyi — 5.2.11.1 Initial Setting

AH500 Module Manual temperature sensor, O n + and I n + have to be short-circuited, and O n - and I n - have to be short-circuited. ( n is in the range of 0 to 7.) *2. If users want to measure the resistance in the range of 0 Ω to 300 Ω, they can use a two-wire or three-wire sensor instead of a four-wire sensor. *3. User need to select an appropriate sensor. If a Ni100 temperature sensor, a Pt100 sensor, and a resistance sensor are used, the internal excitation current is 471.5 μA. If a Ni1000 temperature sensor, and a Pt1000 temperature sensor are used, the internal excitation current is 204.8 μA.

5.2.10 LED Indicators 5.2.11 HWCONFIG in ISPSoft 5.2.11.1 Initial Setting (1) Start ISPSoft, and then double-click HWCONFIG . 5-54 Number Name Description Operating status of the module RUN LED 1 ON: The module is running. indicator OFF: The module stops running. Error status of the module ERROR LED ON: A serious error occurs in the module. 2 indicator OFF: The module is normal. Blink: A slight error occurs in the module.