AH500 Module Manual 13.1 Introduction of AH10PFBS-5A 1. Thank you for choosing Delta AH10PFBS-5A PROFIBUS-DP slave module. To ensure correct installation and operation of the product, please read this operation manual carefully before use. 2. This operation manual only provides introductory information on AH10PFBS-5A. Detailed information about PROFIBUS-DP protocol is not included in this manual. Please refer to relevant literatures for more information on PROFIBUS-DP protocol. 3. AH10PFBS-5A is a PROFIBUS-DP slave module for connecting Delta’s AH500 series CPU module to PROFIBUS-DP network.

It does not need to be externally connected with the power supply since its power is supplied by the rack. 4. The power module AHPS05-5A, an AH500 series PLC and the main rack are necessary for using AH10PFBS-5A. 5. AH10PFBS-5A can only be connected to the I/O slot of the main AH500 series rack instead of the extension rack. 13.1.1 Functions  Supports PROFIBUS-DP cyclic data transmission between the master and multiple slaves  Auto-detects baud rates; supports max. 12 Mbps  Self-diagnosis  Supports hot-plugging (The module could be inserted to or removed from the main rack when the main rack is powered ON.)  The main rack can connect 8 AH10PFBS-5A modules at most.

 The I/O data of each AH10PFBS-5A supports max. 100 words of data input and 100 words of data output. 13.2 Product Profile and Outline 13.2.1 Parts 13-2 1. Model Name 2. Digital Displayer 3. Address switch 4. PROFIBUS-DP COM port 5. RUN indicator 6. NET indicator 7. Set screw 8. Nameplate 9. Module fixing projection