Kaiyi — 13.3.5 PROFIBUS Node Address Setting

AH500 Module Manual 13.3.4 Definition of PROFIBUS-DP Port Pin 5 9 6 1 13.3.5 PROFIBUS Node Address Setting The rotary node address switch of AH10PFBS-5A is used for setting the node address of AH10PFBS-5A on the PROFIBUS-DP network. The rotary node address switch consists of two rotary switches, x16 0 and x16 1 . The range for one rotary switch is 0~F. The range for setting the node address is as the following table is. 1 x16 0 x16 Example: If you need to set the node address of AH10PFBS-5A to 26 (decimal), simply switch the corresponding switch of x16 1 to “1” and the corresponding switch of x16 0 to “A”. 26 (decimal)=1A (hex)=1x16 1 +Ax16 0 . Note:

 Switch OFF the power supply before setting up the node address of AH10PFBS-5A. Repower the module after the setup is completed.  Changing the value on the switch during the operation of AH10PFBS-5A will not be valid immediately until repowering AH10PFBS-5A after powering it OFF.  Use the slotted screwdriver to set up the switch. Be careful not to scratch the module. 13-6 Pin Definition Description 1 -- N/C 2 -- N/C 3 RxD/TxD-P Sending/receiving data (P (B)) 4 -- N/C 5 DGND Signal ground (C) 6 VP Supplying positive voltage 7 -- N/C 8 RxD/TxD-N Sending/receiving data (N (A)) 9 -- N/C Address Definition H’1~H’7D Valid PROFIBUS address H’0 or H’7E~H’FF Invalid PROFIBUS address