Kaiyi — 13.9.5 Configuration on the PROFIBUS-DP Network (Software Configuration)

AH500 Module Manual output D mapping The number of starting D register in output area 100 (Changeable by the keyboard) (Master->Slave) 7. Double click AH10PFBS-5A icon on the PROFIBUS network in “HW Config” dialog box and then the following window pops up. The indication of the above option is shown below. 8. Download the configuration data after configuration of the data is over. After the connection between the master and AH10PFBS-5A is made and the NET light of AH10PFBS-5A is green, it indicates that the communication between AH10PFBS-5A and the PROFIBUS-DP master is normal. Otherwise, shoot the trouble according to the instruction in chapter 8.

13-34 Item Indication Default Input D mapping (Slave->Master) The number of starting D register in input area 0 ( Changeable by the keyboard) Option Selection Indication Los comm. with master Hold I/O data The input and output data before offline will keep unchanged when AH10PFBS-5A and the master are offline (E.g. the PROFIBUS-DP bus connector is removed from the slave). Clear I/O data The output data received from the master will be cleared to 0 and the input data will keep unchanged when AH10PFBS-5A and the master are offline (E.g. the PROFIBUS-DP bus connector is removed from the slave).