AH500 Module Manual 14.4.2 Terminal Resistor When AHRTU-PFBS-5As are installed at the two ends of the PROFIBUS network, their PROFIBUS interfaces need connect the terminal resistors including the following 3 resistors, Rt, Ru and Rd. The standard PROFIBUS connector contains the built-in terminal resistor which user could select whether to connect to the station or not via the switch. User could purchase the standard PROFIBUS connector to add the terminal resistor.
The last stati on 1st station DGND DGND 5 9 A Rd Rd 390Ω Data w ireA 390Ω A 5 4 9 4 8 220Ω B Rt Rt 220Ω 8 3 7 Data w ire B B 3 2 7 2 6 5V Ru Ru 390Ω 390Ω 6 1 B A B A 5V 1 6 7 8 9 6 7 8 9 5 4 3 2 1 5 4 3 2 1 S tati on 2 Station 3 14.4.3 Model and Specification of I/O Modules The following table lists the model and specification of the power module, main rack, extension racks and extension communication cable. 14-8 Model Description AHPS05-5A Power module:
100-240VAC 50/60HZ AHBP04M1-5A 4-slot main rack specially used by CPU/RTU AHBP06M1-5A 6-slot main rack specially used by CPU/RTU AHBP08M1-5A 8-slot main rack specially used by CPU/RTU AHBP12M1-5A 12-slot main rack specially used by CPU/RTU AHBP06E1-5A 6-slot extension rack specially used by CPU/RTU AHBP08E1-5A 8-slot extension rack specially used by CPU/RTU AHACAB06-5A The 0.6m communication cable specially used by the extension rack AHACAB10-5A The 1.0m communication cable specially used by the extension rack AHACAB15-5A The 1.5m communication cable specially used by the extension rack AHACAB30-5A The 3.0m communication cable specially used by the extension rack AHACAB50-5A The 5.0m communication cable specially used by the extension rack AHACABA0-5A The 10.0m communication cable specially used by the extension rack AHACABA5-5A The 15.0m communication cable specially used by the extension rack AHACABB0-5A The 20.0m communication cable specially used by the extension rack AHACABC0-5A The 30.0m communication cable specially used by the extension rack