AH500 Module Manual Settings of the digital modules and special modules connectable to AHRTU-PFBS-5A are introduced below. Settings of all digital modules are same and the following will make the introduction of the setting by taking AH16AP11R-5A as an example. Setting of AH16AP11R-5A After configuring AH16AP11R-5A, refer to Figure 0 for the related parameters setting. Figure 0 Explanation of the options above 14-26 Name Setting Explanation rack 0x01 The number of the rack where the I/O module is (Rack number ranges from 1 to 8, 1 represents the main rack, 2~8 stand for extension racks and the slot number is 0~11.) slot 0x00 The number of the slot on the rack where the I/O module is.
(Rack number ranges from 1 to 8, 1 represents the main rack, 2~8 stand for extension racks and the slot number is 0~11). Output hold disable/enable Output hold options: Enable: the output of other I/O modules of AHRTU-PFBS-5A is held when some I/O module has a fault and the master is disconnected or stops running. Disable: the output of other I/O modules of AHRTU-PFBS-5A is cleared to 0 when some I/O module has a fault and the master is disconnected or stops running.