Chapter 14 Remote I/O Communication Module AHRTU-PFBS Setting of AH08AD-5C After configuring AH08AD-5C, refer to Figure 3 for the related parameters setting. Figure 3 Explanation of the options above 14-29 Name Setting Explanation rack 0x01 The number of the rack where the I/O module is (Rack number ranges from 1 to 8, 1 represents the main rack, 2~8 stand for extension racks and the slot number is 0~11.) slot 0x02 The number of the slot on the rack where the I/O module is. (Rack number ranges from 1 to 8, 1 represents the main rack, 2~8 stand for extension racks and the slot number is 0~11).
CH0~CH7 Input mode disable 0mA~20mA 4mA~20mA +20mA~-20m A The input channel mode of AH08AD-5C is disabled by default. Mode: disable Mode: 0mA~20mA Mode: 4mA~20mA Mode: +20mA~-20mA CH0~CH7 Input average time 0x0A Average times setting for CH0~ CH7 input