Kaiyi — 14.7.2 Configuration of PROFIBUS DP Network

AH500 Module Manual  Setting of AH04PT-5A After configuring AH04PT-5A, refer to Figure 8 for the related parameters setting. Figure 8 14-34 Name Setting Explanation 1V~+5V 0mA~20mA 4mA~20mA Mode: -5V~+5V Mode: 0V~+5V Mode: 1V~+5V Mode: 0mA~20mA Mode: 4mA~20mA CH0~CH3 Input average time 0x0A Average times setting for CH0~ CH3 input CH0~CH1 output hold disable/enable Output hold options: Enable: the output of other I/O modules of AHRTU-PFBS-5A is held when some I/O module has a fault and the master is disconnected or stops running. Disable: the output of other I/O modules of AHRTU-PFBS-5A is cleared to 0 when some I/O module has a fault and the master is disconnected or stops running.