Kaiyi — 14.9.4 Configuration of the Master

Chapter 14 Remote I/O Communication Module AHRTU-PFBS Explanation of the options above  Pick “AH06XA-5A” and the related parameters are displayed as follows. The input modes of CH0~CH3 are all set to -10V~+10V 。 14-65 Name Setting Explanation rack 0x01 The number of the rack where the I/O module are placed (Rack number is 1~8, 1 represents the main rack, 2~8 are extension racks and the slot number is 0~11.) slot 0x00 The number of the slot on the rack where the I/O module is. (Rack number is 1~8, 1 represents the main rack, 2~8 are extension racks and the slot number is 0~11). Output hold disable/enable Output hold options: Enable:

the output of other I/O modules of AHRTU-PFBS-5A is held when some I/O module has a fault and the master is disconnected or stops running. Disable: the output of other I/O modules of AHRTU-PFBS-5A is cleared to 0 when some I/O module has a fault and the master is disconnected or stops running.