AH500 Module Manual 15.4.5 Flowchart Representing the Action of a CANopen Master Station Powering AH10COPM-5A Whether the module is initialized successfully No E rror code A0F5/A0F7 Yes Slave mode Setting AH10COPM-5A by HWCONFIG Maser mode Initializing the slave station AH10COPM-5A Initializing the master station AH10COPM-5A The slave station A H10COPM-5A is ready to operate. The master station A H10COPM-5A is ready to operate. AH10COPM-5A follows the NMT com mand sent by a master station. If AH10COPM-5A is operational, it will exchange CANopen PDOs with a CP U module.
Yes Checking whether a CANopen network is created No E rror code A0F1 Yes Checking whether the actual network is the same as the network created No E rror code A0F6/A0F8 Yes Whether the PDOs in all slave stations are set successfully No E rror code A0E4 Yes Whether the automatic SDOs in all slave stations are set successfully No E rror code A0E3 Yes Whether the heartbeat or node guarding in all slave stations is set successfully No E rror code A0E5 Yes The master station AH10COPM-5A and all slave stations are ready to operate. They do not exchange data. STOP No State of a CPU module RUN The master station A H10COPM-5A and all slave stations are operational.
A CPU module exchanges CANopen P DOs with AH10COPM-5A. 15-22