AH500 Module Manual 15.5.5 Obtaining the States of the Slave Stations on a CANopen Network 1. Function block Users can obtain the states of the slave stations on a CANopen network from the AH10COPM-5A module in a slot on the main backplane used by means of the function block CANopen_Info. 2. Input pins/Output pins 15-32 Input pin Name Function Data Setting value Time when a value is valid type SID Slot number WORD K0~K11 The value of the SID input pin is valid when there is a transition in the Execute input pin’s signal from low to high. Execute The function block is executed when there is a transition in the Execute input pin’s signal from low to high.
BOOL True/False - Output pin Name Function Data type Time when there is Time when there is a transition in an output pin’s signal from high to low a transition in an output pin’s signal from low to high Done The execution of the function block is complete. BOOL There is a transition in the Done output pin’s signal from low to high when the execution of the function block is complete. There is a transition in the Done output pin’s signal from high to low when there is a transition in the Execute input pin’s signal from high to low. If the Execute input pin is set to False when the execution of the function block is complete, the Done output pin will be set to False in the next cycle.