Mitsubishi — 5.6 Descriptions of the Applied Instructions

Chapter 5 Applied Instructions  S 1 : Source device 1; S 2 : Source device 2  The instructions are used to compare the value in S 1 with that in S 2 . Take the instruction AND= for instance. If the comparison result is that the value in S 1 is equal to that in S 2 , the condition of the instruction is met. If the comparison result is that the value in S 1 is not equal to that in S 2 , the condition of the instruction is not met. Explanation  The instruction AND ※ is connected to a contact in series.  If a 32-bit counter is used, the 32-bit insturciton DAND ※ must be used.

If a 32-bit counter and the 16-bit instruction AND ※ are used, ,a program error will occur, and the ERROR LED indicator on the motion control module will blink. (C200~C255 are 32-bit counters.)  When X0.0 is ON and the present value in C10 is equal to K200, Y1.0 is Example ON.  When X0.1 is OFF and the value in D0 is not equal to K-10, Y1.1 is set to ON.  When X0.2 is ON and the value in (D11, D10) is less than 678,493, or when M3 is ON, M50 is ON.

X0.0 AND= Y1.0 X0.1 AND M50 X0.2 DAND> M3 5-113 API Instruction code Operand Function 232~238 D AND※ S , S 1 2 Comparing values Device Xn.n Yn.n M S K 16# F KnM KnS D W T C V Z S 1           S 2           Pulse instruction 16-bit instruction (5 steps) 32-bit instruction (7 steps) –   16-bit instruction 32-bit API No. ON OFF instruction 232 AND= DAND= S =S 1 2 S ≠S 1 2 233 AND> DAND> S >S 1 2 S ≦S 1 2 234 AND< DAND< S <S 1 2 S ≧S 1 2 236 AND<> DAND<> S ≠S 1 2 S =S 1 2 237 AND<= DAND<= S ≦S 1 2 S >S 1 2 238 AND>= DAND>= S ≧S 1 2 S <S 1 2 K200 C10 K-10 D0 SET Y1.1 K678493 D10