Mitsubishi — 10.2 High-speed Timers

AH500 Motion Control Module Manual The program is shown below.  Ladder diagram M1  Function block Example 2: Using C208 in cyclic mode 1. Users have to write K5 into K1SM208 2. C208 is enabled. The interval between the rising edge of a pulse received through X0.2 and the rising edge of the next pulse is measured. The interval is written into C209. (Unit: 0.01 microseconds) t1 t2 C209 C209 Cyclic mode Unit: 0.01 μs The program is shown below.  Ladder diagram M1  Function block 3. The cyclic mode is used to measure a frequency. 10-6 MOVP K4 K1SM208 DCNT C208 K10 .2 MOVP K5 K1SM208 DCNT C208 K10