Chapter 14 DMCNET SR1078, SR1178, SR1278, SR1378, SR1478, SR1578, SR1678, SR1778, SR1878, SR1978, SR2078, SR2178, SR2278, SR2378, SR2478, SR2578: Parameter position in the servo drive for the axis specified on a DMCNET/Way in which the axis specified on a DMCNET returns home [Description] Parameter position in the servo drive for the axis specified on a DMCNET: The value of the high byte in SR1078 (SR1178, SR1278, SR1378…) indicates a group number, and the value of the low byte in SR1078 (SR1178, SR1278, SR1378…) indicates a parameter number.
If users want to use P1-44, the value of the high byte in SR1078 (SR1178, SR1278, SR1378…) will be 1, and value of the low byte in SR1078 (SR1178, SR1278, SR1378…) will be 44, that is, the value in SR1078 (SR1178, SR1278, SR1378…) will be 16#012C. Way in which the axis specified on a DMCNET returns home: Users can set the way in which the axis specified on a DMCNET returns home. The value in SR1078 (SR1178, SR1278, SR1378…) is in the range of 1 to 35. Please refer to section 14.6 for more information about modes of returning home.
14.4 DMCNET Connection Setting a connection 14-7 1st axis 2nd axis 3rd axis 4th axis HW LW HW LW HW LW HW LW - SR1078 - SR1178 - SR1278 - SR1378 5th axis 6th axis 7th axis 8th axis HW LW HW LW HW LW HW LW - SR1478 - SR1578 - SR1678 - SR1778 9th axis 10th axis 11th axis 12th axis HW LW HW LW HW LW HW LW - SR1878 - SR1978 - SR2078 - SR2178 13th axis 14th axis 15th axis 16th axis HW LW HW LW HW LW HW LW - SR2278 - SR2378 - SR2478 - SR2578