Delta Electronics AH500 — 5.1.3 Relation Between the PLC Action and the Device Type

AH500 Operation Manual *1: The decimal forms are notated by K in the device lists in Chapter 5 and Chapter 6 in AH500 Programming Manual, whereas K50 should be inputted in ISPSoft rather than merely 50. *2: The floating-point numbers are notated by F/DF in the device lists in Chapter 5 and Chapter 6 in AH500 Programming Manual, whereas they are represented by decimal points in ISPSoft; for the floating-point F500, one should input 500.0. *3: The strings are notated by “$” in Chapter 5 and Chapter 6 in AH500 Programming Manual, whereas they are represented by “ ” in ISPSoft; for the string of 1234, one should input “ 1234 ” in ISPSoft.

5.1.2 Basic Structure of I/O Storages 5.1.3 Relation Between the PLC Action and the Device Type 5-4 Device Function Access of Access of Modification by Forcing the bit bits words ISPSoft ON/OFF X Input relay OK OK OK OK Y Output relay OK OK OK OK M Auxiliary relay OK - OK NO SM Special auxiliary relay OK - OK NO S stepping relay OK - OK NO T Timer OK OK OK NO C Counter OK OK OK NO HC 32-bit counter OK OK OK NO D Data register OK OK OK NO SR Special data register - OK OK NO L Link register OK OK OK NO E Index register - OK OK NO Device type Non-latched Latched Output relay PLC action area area Power: OFF→ON Cleared Retained Cleared STOP ↓ RUN The output relay is cleared.

Retained Retained Cleared The state of the output relay is retained. Retained Retained Retained The state of the output relay returns to that before the PLC’s stopping. Retained Retained Refer to the settings of device Y The non-latched area is cleared. Cleared Retained Refer to the settings of device Y The state of the latched area is retained. Retained Retained Retained RUN→STOP Retained Retained Retained SM204 is ON. Cleared Retained Cleared (All non-latched areas are cleared.) SM205 is ON. Retained Cleared Retained (All latched areas are cleared.) Default value 0 0 0