AH500 Operation Manual The figure below is an example of a data exchange table. Group #1, group #2, group #4, and group #5 are involved in data exchange. Please refer to the table below for more information. 11-8 Column Description Serial Number (#) The data exchange groups in the data exchange table in the PLC Link Table Editor window are numbered. Users can set 16 data exchange groups or 32 data exchange groups, depending on the model selected. Station Addr. The slave station address which belongs to a data exchange group is indicated. A station address can belong to several data exchange group.
Besides, the station address 0 represents an undefined slave station, and is not a broadcast station address. R/W R: The master station reads the data in devices in a slave station. W: The master station writes data into devices in a slave station. Master Device Data The range of devices which are used in the master station is indicated. : The master station writes data into devices in a slave station. Slave Device Data The devices which are used in a slave station are indicated. If a slave station is a user-defined Modbus device, the devices used will be represented by hexadecimal addresses. Length A data length is indicated. A length indicates the number of devices used.
Status Users can decide whether to involve a data exchange group in data exchange. If a data exchange group is set incorrectly, the data exchange group will not be involved in data exchange. If a data exchange group is not involved in data exchange, the related data will be on a gray ground. Device Type The device types shown are consistent with the device names shown in the working area in NWCONFIG. If a slave station address is assigned to a network module, the name of the PLC to which the network module is connected will be shown. Besides, if a slave station is undefined, it is unknown.
Serial Description number #1 The master station reads the data in D2500~D2599 in the slave station whose station number is 2, and stores the data in D3000~D3099 in itself. Meanwhile, the data in D3100~D3149 in the master station is written into D2600~D2649 in the slave station. #2 The master station reads the data in M3000~M3159 in the slave station whose station number is 2, and stores the data in M3000~M3159 in itself. Meanwhile, the data in M3200~M3359 in the master station is written into M3200~M3359 in the slave station.