AH500 Operation Manual 11.3 Data Exchange Function AH500 series can exchange data with another Ethernet PLC not only by means of instructions, but also by a table interface. An Ethernet PLC can exchange data with another Ethernet PLC not only by means of instructions, but also by a table interface. The data exchange tables which can be used by Ethernet PLCs are not completely the same. Please refer to the table below for more information about the quantity of data which a PLC can read/write, and the devices which can be involved in data exchange. A chart showing data exchange is provided below. Specification table:
11.3.1 MODBUS Data Exchange 11.3.1.1 MODBUS Data Exchange Data exchange between electronic devices can be achieved via MODBUS protocol. Through MODBUS protocol, users can exchange data among Delta devices and any 3 rd party devices, as long as they comply with the MODBUS standard. A chart showing information concerning MODBUS data exchange is provided below. 11.3.1.2 MODBUS Data Exchange - PLC Parameter Setting Double-click HWCONFIG , and then double-click CPU . After CPU is double-clicked, the PLC Parameter Setting window will be opened.
11-60 Communication mode MODBUS Maximum number of 32 connections Communication protocol Standard Modbus and AH500 communication protocol Maximum quantity of data which can be read/written Remote terminal unit AH500 series CPU module 400 words 6400 bits DVP series PLCs 100 words 100 bits Others 100 words 100 bits Supported devices Remote terminal unit AH500 series CPU module X, Y, M, SM, SR, D, T, C, S, E DVP series PLCs X, Y, M, D Others Logical address 0x0000~0xFFFF Supported models AH500 advanced CPU modules (AHCPU511/521/531)