AH500 Operation Manual *1. The maximum number of connections is equal to the number of Modbus TCP data exchange blocks plus the number of Ether Link data exchange blocks. The number of Ether Link data exchange blocks in a PLC is the number of nodes of which the PLC demands data, and the nodes to which the PLC provides data are not counted. 11.3.2.2 MODBUS TCP Data Exchange - PLC Parameter Setting Double-click HWCONFIG , and then double-click CPU . After CPU is double-clicked, the PLC Parameter Setting window will be opened.
11-88 Communication protocol Standard Modbus TCP/IP and AH communication protocol Maximum quantity of data which can be read/written Remote terminal unit AH500 series CPU module 400 words 6400 bits DVP series PLCs 100 words 100 bits Others 100 words 100 bits Supported devices Remote terminal unit AH500 series CPU module X, Y, M, SM, SR, D, T, C, S, E DVP series PLCs X, Y, M, D Others Logical address 0x0000~0xFFFF Supported models AHCPU500-EN, AHCPU510-EN, AHCPU520-EN, AHCPU530-EN, AHCPU511-EN, AHCPU521-EN, AHCPU531-EN