Chapter 12 Troubleshooting 12.2.5 Troubleshooting for EtherNet/IP 12-13 Error Description How to fix them Code 16#B100 I/O Connections Duplicated 1. Check if the system has created the I/O connections. 2. Change the connection type to Listen Only. 16#B106 Ownership Conflict 1. Check the scanner owner. 2. Reconfigure the invalid scanner. 3. Change the connection to multicast. 16#B110 Target for Connection not Configured 1. Check the I/O connection status. 2. Activate the I/O connections again. 16#B111 Adapter RPI Not Supported Check the RPI for the adapter. 16#B113 Out of Connections 1. Check if the connection exceeds the limit. 2. Reduce the number of the product connection.
16#B119 Non-Listen Only Not Opened 1. Check if the system has created the I/O connections. 2. Check the scanner I/O connection status. 16#B127 Invalid Originator to Target Size Check the module number and the product setup file to see if they are matched. 16#B128 Invalid Target to Originator Size Check the output size in the connection parameters. 16#B129 The configuration path parameters in the EDS file are mismatched. 1. Check if the product information and the EDS file are matched. 2. Reload the EDS file. 3. Ask the vendor of the device for the EDS file. 16#B12D Consumed Tag does not exist. Check if the parameters in the consumed tag are correctly set. 16#B12E Produced Tag does not exist.
Check if the parameters in the produced tag are correctly set. 16#B203 I/O Connection Timeout 1. Check the network connection status. 2. Check if the module is working fine. 3. Increase the RPI value. 16#B204 Unconnected Request Timeout No response from the adapter; check if the power and the network connection of the adapter are working properly. 16#B302 Network Bandwidth NOT Available for Data 1. Check the I/O connection limit between the scanner and the adapter. 2. Increase the RPI value or reduce the number of the connections. 16#B315 Invalid Segment in Connection Path Check the module number and the product setup file to see if they are matched.