Delta Electronics AH500 — 12.3.2 Troubleshooting for AH02HC-5A/AH04HC-5A

Chapter 12 Troubleshooting 12-33 Error Description Remedy code 16#A013 The number of cycles set for channel 1 exceeds the range. Check the module parameter in HWCONFIG. The number of cycles set for channel 1 should be in the range of 2 to 60. 16#A014 The comparison value set for channel 1 exceeds the range. Check the module parameter in HWCONFIG. The comparison value set for channel 1 should be in the range of -999999999 to 999999999. 16#A015 A limit value set for channel 1 is incorrect. Check the module parameter in HWCONFIG. A limit value of set for channel 1 should be in the range of -200000 to 200000. 16#A016 The interrupt number set for channel 1 exceeds the range.

Check the module parameter in HWCONFIG. The interrupt number set for channel 1 should be in the range of 0 to 31. 16#A021 The linear accumulation in channel 2 exceeds the range. To clear the linear accumulation, users need to set bit 1 in CR56 to ON by means of FROM/TO. 16#A022 The scale set for channel 2 exceeds the range. Check the module parameter in HWCONFIG. The scale set for channel 2 should be in the range of 0 to 32767. 16#A023 The number of cycles set for channel 2 exceeds the range. Check the module parameter in HWCONFIG. The number of cycles set for channel 2 should be in the range of 2 to 60. 16#A024 The comparison value set for channel 2 exceeds the range.

Check the module parameter in HWCONFIG. The comparison value set for channel 2 should be in the range of -999999999 to 999999999. 16#A025 A limit value set for channel 2 is incorrect. Check the module parameter in HWCONFIG. A limit value of set for channel 2 should be in the range of -200000 to 200000. 16#A026 The interrupt number set for channel 2 exceeds the range. Check the module parameter in HWCONFIG. The interrupt number set for channel 2 should be in the range of 0 to 31. 16#A031 The linear accumulation in channel 3 exceeds the range. To clear the linear accumulation, users need to set bit 1 in CR84 to ON by means of FROM/TO. 16#A032 The scale set for channel 3exceeds the range.

Check the module parameter in HWCONFIG. The scale set for channel 3 should be in the range of 0 to 32767. 16#A033 The number of cycles set for channel 3 exceeds the range. Check the module parameter in HWCONFIG. The number of cycles set for channel 3 should be in the range of 2 to 60. 16#A034 The comparison value set for channel 3 exceeds the range. Check the module parameter in HWCONFIG. The comparison value set for channel 3 should be in the range of -999999999 to 999999999. 16#A035 A limit value set for channel 3 is incorrect. Check the module parameter in HWCONFIG. A limit value of set for channel 3 should be in the range of -200000 to 200000.

16#A036 The interrupt number set for channel 3 exceeds the range. Check the module parameter in HWCONFIG. The interrupt number set for channel 3 should be in the range of 0 to 31.