Chapter 12 Troubleshooting 12.3.6 Troubleshooting for AH10SCM-5A 12.3.7 Troubleshooting for AH10DNET-5A The parameters which are mentioned in the table below are set in DeviceNet Builder version 1.07 or above. 12-37 Error Description Remedy code 16#A401 Hardware error Please restore the hardware to the factory setting. If the error still occurs, please contact the factory. 16#A402 The initialization of the system fails. Please restore the system to the factory setting. If the error still occurs, please contact the factory. Error Description Remedy code 16#A002 The setting of the UD Link is incorrect, or the communication fails. Check the setting in SCMSoft, and download the setting again.
16#A401 Hardware error Please contact the factory. 16#A804 The communication through the communication port is incorrect. 1. Check whether the communication cable is connected well. 2. Check the parameter in HWCONFIG, and the parameter. Download the parameter again. 16#A808 Modbus communication error 1. Check whether the communication cable is connected well. 2. Check the parameter in HWCONFIG, and the parameter. Download the parameter again. Error Description Remedy code 16#A0F0 The node ID of AH10DNET-5A is the same as other node ID on the network, or exceeds the range. Make sure that the node ID of AH10DNET-5A is the only one on the network.
If the node ID of AH10DNET-5A is not the only one on the network, please change the node ID, and supply power to AH10DNET-5 again. 16#A0F1 No slave is put on the scan list of AH10DNET-5A. Put slaves on the scan list, and then download the scan list to AH10DNET-5A. 16#A0F2 The working voltage of AH10DNET-5A is low. Check whether the working voltage of AH10DNET-5A and that of an AH500 series CPU module are normal. 16#A0F3 AH10DNET-5A enters the test mode. Switch IN 1 on the module OFF, and supply power to AH10DNET-5A again. 16#A0F4 The bus of AH10DNET-5A becomes OFF. 1. Check whether the communication cable is normal, and whether the shielded cable is grounded. 2.
Check whether the serial transmission speeds of other devices on the network are the same. 3. Check whether the both ends of the cable are connected to 121 Ω terminal resistors. 4. Supply power to AH10DNET-5A again. 16#A0F5 AH10DNET-5A detects that there is no power supply to the DeviceNet network. Check whether the communication cable is normal, and whether the network power supply is normal. 16#A0F6 Something is wrong with the internal memory of AH10DNET-5A. Supply power to AH10DNET-5A again. If the error still occurs, please contact the factory.