AH500 Operation Manual 12-48 Error code Description CPU Status LED indicator status ERROR BUS FAULT 16#6501 The remote device involved in the data exchange does not respond after the timeout period. (SM828~SM955) Continue OFF OFF 16#6502 The remote device involved in the data exchange does not respond correctly. (SM828~SM955) Continue OFF OFF 16#6700 An error occurs when a Modbus TCP data exchange is initialized. Continue Keep Keep 16#6701 Modbus TCP data exchange timeout Continue Keep Keep 16#6702 The data received by means of a Modbus TCP data exchange is incorrect. Continue Keep Keep 16#7002 The CPU module does not support the function.
Continue Keep Keep 16#7203 Invalid access code Continue Keep Keep 16#7401 Function code error Continue Keep Keep 16#7402 The size of a packet exceeds the maximum data length. Continue Keep Keep 16#7404 Packet format error Continue Keep Keep 16#7405 The number of bytes is incorrect. Continue Keep Keep 16#7406 Checksum error Continue Keep Keep 16#7407 There are non-ASCII characters in a command. Continue Keep Keep 16#7408 The PLC is running. Continue Keep Keep 16#740A Data is being written to the memory in the PLC or data fails to be written to the memory in the PLC. Continue Keep Keep 16#740B The CPU module is being reset, or the values in the laching devices are being cleared.
Continue Keep Keep 16#740E An error occurs when the the data in the memory in the PLC is cleared. Continue Keep Keep 16#740F Communication timeout Continue Keep Keep 16#7410 The function code in a reply command is incorrect. Continue Keep Keep 16#7412 Owing to the fact that SW1 is ON, data can not be downloaded to the CPU module. Continue Keep Keep 16#757D The remaining number of PLC password guesses is 0. Continue Keep Keep 16#757E The PLC password entered is incorrect. Continue Keep Keep 16#8522 A module configuration is being scanned. Continue Keep Keep 16#853B An I/O module is not configured. Continue Keep Keep 16#853C An I/O module does not exist.
Continue Keep Keep 16#854B An I/O module is not configured. Continue Keep Keep 16#854C An I/O module does not exist. Continue Keep Keep 16#85E2 An I/O interrupt service routine does not exist. Continue Keep Keep 16#9A01 The setting of the data exchange for slave 1 in the PLC Link is incorrect. (SM1590) Continue Keep Keep 16#9A02 The setting of the data exchange for slave 2 in the PLC Link is incorrect. (SM1590) Continue Keep Keep