Delta AH500 — 6.17.2 Explanation of Real-time Clock Instructions

AH500 Programming Manual Additional remark: 1. If S +2 exceeds the device range, the instruction is not executed, SM0 is ON, and the error code in SR0 is 16#2003. 2. If D +2 exceeds the device range, the instruction is not executed, SM0 is ON, and the error code in SR0 is 16#2003. 3. If the value in S exceeds the range, the operation error occurs, the instruction is not executed, SM0 is ON, and the error code in SR0 is 16#2003. 4. If the values in S 1 ~ S 3 exceed the range, the operation error occurs, the instruction is not executed, SM0 is ON, and the error code in SR0 is 16#2003. 5. If users declare the operand D in ISPSoft, the data type will be ARRAY [3] of BOOL. 6-374