Delta AH500 — 6.19.2 Explanation of Communication Instructions

AH500 Programming Manual The PLC sends the data. LRC CHK (01) above is the error checking code. It can be calculated by means of the instruction LRC. (8-bit mode: SM606 is ON.) LRC check code: 16#01+16#03+16#21+16#01+16#00+16#06=16#2C The two’s complement of 16#2C is 16#D4. ‘D’ (16#44) is stored in the low 8-bit in D113, and ‘4’ (16#34) is stored in the low 8-bit in D114. Additional remark: 1. The format of the communication data in the ASCII mode: 6-412 Register Data Description D100 Low 8 bits ‘:’ 16#3A STX D101 Low 8 bits ‘0’ 16#30 ADR 1 AD (1, 0) is the station address of the AC motor drive. D102 Low 8 bits ‘1’ 16#31 ADR 0 D103 Low 8 bits ‘0’ 16#30 CMD 1 CMD (10) is the command code.

D104 Low 8 bits ‘3’ 16#33 CMD 0 D105 Low 8 bits ‘2’ 16#32 Initial data address D106 Low 8 bits ‘1’ 16#31 D107 Low 8 bits ‘0’ 16#30 D108 Low 8 bits ‘1’ 16#31 D109 Low 8 bits ‘0’ 16#30 Number of data (counted by the word) D110 Low 8 bits ‘0’ 16#30 D111 Low 8 bits ‘0’ 16#30 D112 Low 8 bits ‘6’ 16#36 D113 Low 8 bits ‘D’ 16#44 LRC CHK 0 LRC CHK (01) is the error checking code. D114 Low 8 bits ‘4’ 16#34 LRC CHK 1 D115 Low 8 bits CR 16#0D END D116 Low 8 bits LF 16#0A