AH500 Programming Manual 7. If the number of devices starting from S 2 is not equal to the value in S 3 , the instruction will not be executed, SM0 will be ON, and the error code in SR0 will be 16#2003. 8. If the value in D 2 is not in the range of 0 to 6, the instruction will not be executed, SM0 will be ON, and the error code in SR0 will be 16#2003. 9. If the value in D 2 is 6, and the number of devices starting from D 1 is not equal to the value in D 2 +1, the instruction will not be executed, SM0 will be ON, and the error code in SR0 will be 16#2003. 10.
If the value in S 2 is in the range of 1 to 5, and the quantity of data received is greater than the number of devices starting from D 1 , the data which can not be stored will be ignored. 11. If a completion flag is ON, the PLC will stop receiving data. If a communication port receives data when a completion flag is ON, the data will not be received. 12. If the setting value in S 3 is less than 0 or greater than 1000, the instruction will not be executed, SM0 will be ON, and the error code in SR0 will be 16#2003. 6-428