AH500 Programming Manual 6-169 Device number Function Setting range Description MOUT AUTO _ MOUT automatic change mode True: Automatic The MOUT varies with the MV. False: Normal The MOUT deos not vary with the MV. Cycle Sampling time (T ) S 1~2,000 (unit: 10ms) When the instruction is scanned, the PID algorithm is implmented according to the sampling time, and the MV is refreshed. If T is less than 1, S it will be count as 1. If T is S larger than 2000, it will be count as 2000. When the instruction PID is used in the interval interrupt task, the sampling time is the same as the interval between the timed interrupt tasks.
K p Proportional gain (K ) p Range of positive single-precision floating-point numbers It is the magnified proportional value of the error between the SV and the PV. If the magnified proportional value of the error is less than 0, the K will be count as 0. p K i Integral gain (K) i Range of positive single-precision floating-point numbers It is the integral gain (K). If i the integral gain is less than 0, the K will be count as 0. i K d Derivative gain (K ) d Range of positive single-precision floating-point numbers It is the derivative gain (K ). If d the derivative gain is less than 0, the K will be count as d 0. PID DIR _ PID forward/reverse direction True: Reverse action (E=SV-PV) False:
Forward action (E=PV-SV) ERR DBW _ Range within which the error value is count as 0 Range of single-precisio n floating-point numbers The error value (E) is the difference between the SV and the PV. When the setting value is 0, the function is not enabled. For example, the E within the range between -5 and 5 will be count as 0 if the setting value is 5 or -5. MV MAX _ Maximum output value Range of single-precisio n floating-point numbers Suppose MV MAX is set to _ 1,000. When the MV is larger than 1,000, 1,000 is output. The value in MV MAX should _ be larger than that in MV MIN. Otherwise, the _ maximum MV and the minimum MV will be reversed.
MV MIN _ Minimum output value Range of single-precisio n floating-point numbers Suppose MV MIN is set to _ -1,000. When the MV is less than -1,000, -1,000 is output.