Chapter 6 Applied Instructions complete, SM694 is ON for a scan cycle. 3. The outputs Y0.0~Y0.3 must be transistors. X1.0 Cyclic action Y0.0 0.1s 0.1s 0.1s Y0.1 0.1s Y0.2 0.1s Interruption Y0.3 0.1s The execution of the insturciton is complete. 4. The DIP switches: SM694 Binary-coded decimal wiring of DIP switches A diode (1N4148) must be connected in series. First DIP switch Second DIP swtich Note: The transistor output module AH16AP11T-5A is used in this example. Additional remark: 1. If n exceeds the range, the instruction is not executed, SM0 is ON, and the error code in SR0 is 16#200B. 2. If users declare the operand D 1 in ISPSoft, the data type will be ARRAY [4] of BOOL.
6-370 100 101 102 103 + 1 2 4 8 1 2 4 8 100 101 102 103 X0.0 X0.1 X0.2 X0.3 X0.4 X0.5 X0.6 X0.7 S/S Y0.0 Y0.1 Y0.2 Y0.3 UP ZP 100 101 102 103 1 2 4 8 1 2 4 8 100 101 102 + 103 X0.0 X0.1 X0.2 X0.3 X0.4 X0.5 X0.6 X0.7 S/S Y0.0 Y0.1 Y0.2 Y0.3 UP ZP