Kaiyi — 6.19.2 Explanation of Communication Instructions

AH500 Programming Manual Example 4: 1. Function code 05 (16#05): The AH500 series PLC writes the state into a bit device in the ES2 series PLC. The AH500 series PLC is connected to the ES2 series PLC. (ASCII mode: SM210 is OFF.) The AH500 series PLC is connected to the ES2 series PLC. (RTU mode: SM210 is ON.) 2. ASCII Mode: The AH500 series PLC is connected to the ES2 series PLC. When SM96 and X0.0 are on, the AH500 series PLC sends and receives the following commands. AH  ES2 The AH500 series PLC sends “ : 00 05 0500 FF00 F7 CR LF”. The AH500 series PLC receives “ : 00 05 0500 FF00 F7 CR LF”. ES2  AH The communication command which the AH500 series PLC sends:

6-415 Data Description ‘0’ 16#30 ADR 1 ADR (10) is the station address of the slave. ‘0’ 16#30 ADR 0 ‘0’ 16#30 CMD 1 CMD (10) is the command code. ‘5’ 16#35 CMD 0 0’ 16#30 Initial data address ‘5’ 16#35 ‘0’ 16#30 ‘0’ 16#30 ‘F’ 16#46 Output value ‘F’ 16#46 ‘0’ 16#30 ‘0’ 16#30 ‘F’ 16#46 LRC CHK 1 LRC CHK (01) is the error checking code. ‘7’ 16#37 LRC CHK 0