Chapter 7 Error Codes 7-3 Error code Description CPU Status LED indicator status ERROR BUS FAULT 16#0016 The module setting is incorrect. (SM10) Stop ON OFF 16#0017 The device which is associated with the data register is incorrect. (SM10) Stop ON OFF 16#0018 The serial port is abnormal. (SM9) Keep Blink OFF 16#0019 The USB is abnormal. (SM9) Keep Blink OFF 16#001B Timed interrupt 0 is set incorrectly. Stop ON OFF 16#001C Timed interrupt 1 is set incorrectly. Stop ON OFF 16#001D Timed interrupt 2 is set incorrectly. Stop ON OFF 16#001E Timed interrupt 3 is set incorrectly. Stop ON OFF 16#001F The watchdog timer is set incorrectly.
Stop ON OFF 16#0020 The setting of the fixed scan time is incorrect. Stop ON OFF 16#0021 The setting of the fixed scan time is incorrect. Stop ON OFF 16#0022 The CPU parameter downloaded to the PLC is incorrect. Stop ON OFF 16#0033 The communication setting of COM1 is incorrect. (SM9) Keep Blink OFF 16#0034 The setting of the station address of COM1 is incorrect. (SM9) Keep Blink OFF 16#0035 The setting of the communication type of COM1 is incorrect. (SM9) Keep Blink OFF 16#0036 The interval of retrying the sending of the command through COM1 is set incorrectly.(SM9) Keep Blink OFF 16#0037 The number of times the sending of the command through COM1 is retried is set incorrectly.
(SM9) Keep Blink OFF 16#0038 The communication setting of COM2 is incorrect. (SM9) Keep Blink OFF 16#0039 The setting of the station address of COM2 is incorrect. (SM9) Keep Blink OFF 16#003A The setting of the communication type of COM2 is incorrect. (SM9) Keep Blink OFF 16#003B The interval of retrying the sending of the command through COM2 is set incorrectly.(SM9) Keep Blink OFF 16#003C The number of times the sending of the command through COM2 is retried is set incorrectly. (SM9) Keep Blink OFF 16#0050 The memories in the latched special auxiliary relays are abnormal. Stop ON OFF 16#0051 The latched special data registers are abnormal.
Stop ON OFF 16#0052 The memories in the latched auxiliary relays are abnormal. Stop ON OFF 16#0053 The latched timers are abnormal. Stop ON OFF 16#0054 The latched counters are abnormal. Stop ON OFF 16#0055 The latched 32-bit counters are abnormal. Stop ON OFF 16#0056 The memories in the latched timers are abnormal. Stop ON OFF