Chapter 7 Error Codes 7-9 Error code Description CPU Status LED indicator status ERROR BUS FAULT 16#8F08 Routing instruction error: There is a response timeout. Keep OFF OFF 16#8F09 Routing instruction error: The number of routing connections reaches the upper limit. Keep OFF OFF 16#8105 The contents of the program downloaded are incorrect. The program syntax is incorrect. Keep OFF OFF 16#8106 The contents of the program downloaded are incorrect. The length of the execution code exceeds the limit. Keep OFF OFF 16#8107 The contents of the program downloaded are incorrect. The length of the source code exceeds the limit.
Keep OFF OFF 16#820E The communication port parameter downloaded is incorrect. The communication protocol is incorrect. Keep OFF OFF 16#820F The communication port parameter downloaded is incorrect. The setting of the station address is incorrect. Keep OFF OFF 16#8210 The communication port parameter downloaded is incorrect. The choice among RS-232, RS-485, and SR-422 is incorrect. Keep OFF OFF 16#8211 The communication port parameter downloaded is incorrect. The interval of retrying the sending of the command is set incorrectly. Keep OFF OFF 16#8212 The communication port parameter downloaded is incorrect. The number of times the sending of the command is retried is set incorrectly.
Keep OFF OFF 16#8215 The CPU parameter downloaded is incorrect. The interval of executing interrupt 0 is set incorrectly. Keep OFF OFF 16#8216 The CPU parameter downloaded is incorrect. The interval of executing interrupt 1 is set incorrectly. Keep OFF OFF 16#8217 The CPU parameter downloaded is incorrect. The interval of executing interrupt 2 is set incorrectly. Keep OFF OFF 16#8218 The CPU parameter downloaded is incorrect. The interval of executing interrupt 3 is set incorrectly. Keep OFF OFF 16#8219 The CPU parameter downloaded is incorrect. The watchdog timer is set incorrectly. Keep OFF OFF 16#821A The CPU parameter downloaded is incorrect. The setting of the scan time is incorrect.
Keep OFF OFF 16#821B The CPU parameter downloaded is incorrect. The setting of the remote execution function is incorrect. Keep OFF OFF