Kaiyi — 2.2.15 Refresh Time of Special Data Registers

Chapter 2 Devices Note: As to the SR numbers marked “*”, users can refer to the additional remarks on special auxiliary relays/special data registers.

2.2.15 Refresh Time of Special Data Registers 2-73 CPU5X0-RS2 CPU5X0-EN OFF STOP RUN SR Function    Attribute Default ON RUN STOP *SR1532 ↓ SR1595 Device address in slave 1 from which the data is read in the PLC Link (SR1532 and SR1533) ↓ Device address in slave 32 from which the data is read in the PLC Link (SR1594 and SR1595) ○ ○ – – – R/W 0 *SR1596 ↓ SR1659 Device address in slave 1 into which the data is written in the PLC Link (SR1596 and SR1597) ↓ Device address in slave 32 into which the data is written in the PLC Link (SR1658 and SR1659) ○ ○ – – – R/W 0 *SR1660 ↓ SR1691 Number of data which is read from slave 1 in the PLC Link ↓ Number of data which is read from slave 32 in the PLC Link ○ ○ – – – R/W 0 *SR1692 ↓ SR1723 Number of data which is written into slave 1 in the PLC Link ↓ Number of data which is written into slave 32 in the PLC Link ○ ○ – – – R/W 0 *SR1724 ↓ SR1755 Type of slave 1 in the PLC Link ↓ Type of slave 32 in the PLC Link ○ ○ – – – R/W 0 *SR1756 ↓ SR1787 Address of slave 1 in the PLC Link ↓ Address of slave 32 in the PLC Link ○ ○ – – – R/W 1 ↓ 32 *SR1792 ↓ SR2047 IP address of block 1 in the Ether Link (SR1792 and SR1793) ↓ IP address of block 128 in the Ether Link (SR2046 and SR2047) X ○ – – – R 0 Special data register Refresh time SR0~SR2 The register is refreshed when the program is executed in error.

SR4 SR4 is refreshed when there is a grammar check error SR5~SR6 The register is refreshed when the program is downloaded to the PLC, or when the PLC is suppied with power and starts to run for the first time. SR8 SR8 is refreshed when there is a watchdog timer error. SR40~SR161 The register is refreshed when an error occurs. SR201~SR216 Users set the value and clear it. SR220~SR226 The register is refreshed every scan cycle.