Delta Electronics — 4.3.1 Start Addresses for Digital Input/Output Modules

AS Series Hardware Manual 4.3.1 Start Addresses for Digital Input/Output Modules The remote module AS00SCM-A can connect to up to eight modules on its right side. HWCONFIG automatically assigns input and output devices to a digital input/output module in ISPSoft according to the number of inputs/outputs in the digital input/output module (X1.0–X1.15, X2.0–X2.15… ; Y0.0–Y0.15, Y1.0– Y1.15, Y2.0–Y2.15). The default start addresses are shown below. Note: each digital I/O module reserves 20 words of data devices and it assigns consecutive data devices automatically starting from D29000.  08AM: There are eight inputs.

The input device range occupies 16 bits (X n .0–X n .15) and 20 words of data devices.  08AN: There are eight outputs. The output device range occupies 16 bits (Y n .0–Y n .15) and 20 words of data devices. _4  16AM: There are 16 inputs. The input device range occupies 16 bits (X n .0–X n .15) and 20 words of data devices.  16AN: There are 16 outputs. The output device range occupies 16 bits (Y n .0–Y n .15) and and 20 words of data devices.  16AP: There are eight inputs and eight outputs. The input and output device range occupies 16 bits. (X n .0–X n .15), (Y n .0–Y n .15) and 20 words of data devices.  32AM: There are 32 inputs.

The input device range occupies 32 bits (X n .0–X n+1 .15) and 20 words of data devices.  32AN: There are 32 outputs. The output device range occupies 32 bits (Y n .0–Y n+1 .15) and 20 words of data devices.  64AM: There are 64 inputs. The input device range occupies 64 bits (X n .0–X n+3 .15) and 20 words of data devices.  64AN: There are 64 outputs. The output device range occupies 64 bits (Y n .0–Y n+3 .15) and 20 words of data devices. 4-14