Delta Electronics — 5.1 Wiring

Chapter 5 Wiring (4) Keep the input cables, output cables, and power cable separate from one another. (5) If the main circuit and the power cable cannot be separated from each other, use a shielded cable, and ground it at the side of the I/O module. In some cases, the shielded cable can be grounded at the opposite side. Load through which the Shielded cable alternating current passes AC power supply (6) If you wire a module through conduit, you must ground the conduit correctly. (7) Keep 24 VDC input cables separate from 110 VAC input cables and 220 VDC input cables.

(8) If the wiring length is more than 200 meters (656.19 feet), leakage current can result from parasitic capacitance, and the system will not function properly. Notes on the power cable wiring 5_ (1) Use 110 V/220 V power cable and the 24 VDC power cable with a diameter of 22-18AWG and with less than 2 mm pin-type terminals. Be sure to twist the power cables at the terminal screws. To prevent a short circuit from loose screws, you must use solderless terminals with insulation sleeves. 22-18AWG 11-12mm (2) If cables are connected to the terminals LG and FG, you must ground the cables. Do not connect LG and FG to any devices.

If LG and FG are not grounded, the PLC will be susceptible to noise. Since LG carries electric potential, you will get an electric shock if you touch the metal parts.