Delta Electronics — 5.6.4 Wiring AS04DA-A

Chapter 5 Wiring 5.6.4 Wiring AS04DA-A Voltage output CHX -10V~+10V *4 *2 CH1 VO1 IO1 AG AC m otor drive, recorder, proportioning valve Shielded cable*1 SLD AG Current output CHX 0mA~20mA CH4 *4 AG *3 24VDC DC/DC +15V -15V AG 24V Con ve rte r 5_ *1. Use shielded cables to isolate the analog input signal cable from other power cables. *2. If noise in the input voltage results in noise interference in the wiring, connect the module to a capacitor with a capacitance between 0.1–0.47 μF with a working voltage of 25 V. *3. Connect the SLD to FE. Connect FE and the terminal to ground. *4. Every channel can work with the wiring shown above.

VO4 IO4 AG SLD AC motor drive, recorder, proporti oni ng val ve Shielded cable*1 FE 0V