AS Series Hardware Manual * Please refer to the Module Manual for more information related to the LED indicators on the extension modules. 8.3 Periodic Maintenance In addition to daily inspection, you should perform periodic maintenance depending on the actual operating environment. After making sure that the ambient environment and the AS Series system conform to the cautions listed in Section 8.1, perform the periodic inspection described below. If you find any problems, follow the solution and perform any necessary maintenance. _8 8.3.1 Required Inspection Tools A screwdriver Industrial alcohol A clean cotton cloth A multimeter A thermometer A hygrometer 8-4 No.
Item Inspection Criterion Remedy 5 Power supply module POWER LED indicator Check whether the POWER LED indicator is ON. The POWER LED indicator must be ON. Please refer to Chapter 9 for more information about troubleshooting. CPU module RUN LED indicator When the CPU module is running, check whether the RUN LED is ON. The RUN LED indicator must be ON. ERROR LED indicator Check whether the ERROR LED indicator is OFF. The ERROR LED indicator must be OFF. BUS FAULT LED indicator Check whether the BUS FAULT LED indicator is OFF. The BUS FAULT LED indicator must be OFF. SYSTEM LED indicator Check whether the SYSTEM LED indicator is OFF. The SYSTEM LED indicator must be OFF.
LED indicators on an extension module* Check whether the LED indicators on the extension module are ON. If the LED indicators are ON, the module is operating normally.