AS Series Hardware Manual _9 9-14 6209 The remote communication IP address set in the UDP socket function is illegal. 1. Check the program and the related special data registers. 2. Set the Ethernet parameter for the CPU module in HWCONFIG CPU Module > Device Setting > Options > Ethernet Port Advanced > UDP Socket. - X 620A The local communication port set in the UDP socket function is illegal. 1. Check the program and the related special data registers. 2. Set the Ethernet parameter for the CPU module in HWCONFIG CPU Module > Device Setting > Options > Ethernet Port Advanced > UDP Socket. - X 620C The device from which the data is sent in the UDP socket function is illegal. 1.
Check the program and the related special data registers. 2. Set the Ethernet parameter for the CPU module in HWCONFIG CPU Module > Device Setting > Options > Ethernet Port Advanced > UDP Socket. - X 620F The device which receives the data in the UDP socket function is illegal. 1. Check the program and the related special data registers. 2. Set the Ethernet parameter for the CPU module in HWCONFIG CPU Module > Device Setting > Options > Ethernet Port Advanced > UDP Socket. - X 6210 The data received through the UDP socket exceeds the device range. 1. Check the program and the related special data registers. 2.
Set the Ethernet parameter for the CPU module in HWCONFIG CPU Module > Device Setting > Options > Ethernet Port Advanced > UDP Socket. - X 6212 There is no response from the remote device after the timeout period. Make sure that the remote device is connected. - X 6213 The data received exceeds the limit. 1. Check the program and the related special data registers. 2. Set the Ethernet parameter for the CPU module in HWCONFIG CPU Module > Device Setting > Options > Ethernet Port Advanced > UDP Socket. - X 6214 The remote device refuses the connection. Make sure the remote device operates normally. - X 6215 The socket is not opened. Check whether operational sequence in the program is correct.
- X 6217 The socket is opened. Check whether operational sequence in the program is correct. - X 6218 The data has been sent through the socket. Check whether operational sequence in the program is correct. - X 6219 The data has been received through the socket. Check whether operational sequence in the program is correct. - X 621A The socket is closed. Check whether operational sequence in the program is correct. - X 7011 The device communication function code in COM1 is incorrect. 1. Check the communication setting in the master and the slave. 2. Check the communication cable. - H